National Full Line Stocking Distributor of Wire & Cable
Calvert Wire & Cable - Solutions for Industry, Construction, Utility, Datacom
Home | Products | Request Quote | Events | Contact |  Search  
Call 800.837.2668 to order, request a quote or for more info

 Products
   600v-35kv Power
   Low Voltage
   Control & Instrumentation
   High Temperature
   Flexible and Portable
   Transportation
   Voice, Data & Video
   Cable Management
   Termination & Splice

 Markets
   Industrial / MRO
   Construction
   Utility
   Datacom
   Traffic & Roadway
   OEM

 Services
 Manufacturer Links
 Resources
 About
 Contact
 Events
 Request Quote
 Careers




Resources
Flame Test Standards

FT1 Vertical Flame Test
per C.S.A. C22.2 No. 0.3-92 Para 4.11.1
A finished cable shall not propagate a flame or continue to burn for more than one (1) minute after five (5) fifteen (15) second applications of the test flame. There is an interval of fifteen (15) seconds between flame applications. The flame test shall be performed in accordance with Para 4.11.1 of Canadian Standards Association (CSA) Standard C22.2 No. 0.3. In addition, if more than 25% of the indicator flag is burned, the test cable fails.


FT4 Vertical Flame Test
Cables in Cable Trays per C.S.A. C22.2 No. 0.3-92 Para 4.11.4
Similar to the UL-1581 Vertical Tray Flame Test, but is more severe. The FT4 test has its burner mounted at 20° from the horizontal with the burner ports facing up. The UL-1581 Vertical Tray has its burner at 0° from the horizontal. The FT4 samples must be larger than 13mm (.512") in diameter.

If not, then the cable samples are grouped in units of at least three (3) to obtain a grouped overall diameter of 13mm. The UL-1581 Vertical Tray does not distinguish on cable size. The FT4 has a maximum char height of 1.5 m (59") measured from the lower edge of the burner face. The UL-1581 has a flame height allowable up to approximately 78" measured from the burner.



FT6 Horizontal Flame & Smoke Test
per C.S.A. C22.2 No. 0.3-92 Appendix B
Cables passing the FT6 Horizontal Flame and Smoke Test are designated FT6 in the column where the trade number appears. This test is for cables which must pass a Horizontal Flame and Smoke Test in accordance with ANSI/NFPA Standard 262-1985 (UL-910). The maximum flame spread shall be 1.50 meters (4.92 ft.). The smoke density shall be 0.5 at peak optical density and 0.15 at maximum average optical density.


Back to previous page



The information provided in the resources section is intended for reference only. There is no guarantee, written or implied, regarding the accuracy of the information provided.
Calvert Wire & Cable


call today 800.837.2668 <> fax 216.433.7614
Terms & Conditions | Privacy Policy | Site Map © 2010 Calvert Wire & Cable All Rights Reserved
5091 West 164th Street | Brook Park, Oh 44142